Criteria for Solenoid Valve Selection

The selection of a solenoid valve should primarily follow four key principles: safety, reliability, suitability, and economy. Furthermore, the selection process must account for six specific on-site operating conditions: pipeline parameters, fluid parameters, pressure parameters, electrical parameters, actuation method, and any special requirements.

 

Selection Criteria:
1. Pipeline Parameters (for determining nominal diameter/DN and connection type):
1) Determine the nominal diameter (DN) based on the internal diameter of the on-site pipeline or the required flow rate.
2) Regarding connection type: for sizes greater than DN50, flanged connections are generally required; for sizes DN50 or smaller, the connection type can be selected according to the user's preference.

 

2. Fluid Parameters (for determining material and temperature rating):
1) For corrosive fluids, use corrosion-resistant solenoid valves or those made entirely of stainless steel. For food-grade or ultra-clean fluids, use solenoid valves made of food-grade stainless steel.
2) For high-temperature fluids, select solenoid valves constructed with high-temperature-resistant electrical and sealing materials, utilizing a piston-style design.
3) Consider the fluid state (gaseous, liquid, or mixed); this is particularly important for valves with a nominal diameter greater than DN25.
4) For fluid viscosity: generally, any type can be used if the viscosity is below 50 cSt; if it exceeds this value, a solenoid valve designed for high-viscosity fluids must be selected.

 

3. Pressure Parameters (for determining operating principle and structural type):
1) Nominal pressure: This parameter follows the same definition as that used for other general-purpose valves and is determined by the nominal pressure of the pipeline.
2) Operating pressure: If the operating pressure is low, a direct-acting or semi-direct-acting (step-direct-acting) valve must be used. If the minimum operating pressure differential is 0.04 MPa or greater, direct-acting, semi-direct-acting, or pilot-operated valves are all suitable.

 

4. Electrical Parameters: For voltage specifications, AC220V or DC24V are the preferred and most convenient choices.

 

5. Selection based on duration of operation: Normally Closed (NC), Normally Open (NO), or designed for continuous energization.
1) If a solenoid valve needs to remain open for long periods-specifically, if the time spent in the open state exceeds the time spent in the closed state-a Normally Open (NO) type should be selected.
2) If the valve is open for only short periods, or if the durations of the open and closed states are roughly equal, a Normally Closed (NC) type should be selected.
3) However, for applications involving safety protection-such as flame monitoring in furnaces or kilns-a Normally Open (NO) type must not be used; instead, a model designed for continuous, long-term energization should be chosen.

 

6. Selection based on environmental requirements and auxiliary functions: explosion-proof, check-valve (non-return) capability, manual override, moisture/mist resistance, water-spray resistance, or submersible capability.